A thermal image of a PV installation shows in a single flyover which panels, cells or strings are warmer than the rest. That is valuable. But a thermal capture taken under the wrong conditions produces an attractive colour image in which nothing can be seen. Or worse: anomalies that do not exist.
The difference between the two comes down to three things you can check beforehand.
Why a defective panel gets warmer
A solar cell that delivers power stays relatively cool. A cell that can no longer deliver power, for example due to a crack, a loose connection or a faulty bypass diode, converts the energy it receives into heat. That cell becomes a hotspot. A complete string that is not working produces a pattern of warm panels next to each other.
These temperature differences only arise when the installation is in operation and receives sufficient sunlight. No current, no difference, and no difference, no finding.
The three conditions
The technical specification IEC TS 62446-3 defines when a thermal inspection of a PV installation is reliable. The main conditions:
- Irradiance of at least 600 W/m² on the plane of the panels. Below that, the temperature differences become too small and faults disappear into the measurement noise.
- Little wind. Wind cools the panels and masks hotspots. The standard sets an upper limit of approximately 28 km/h. Our own flight limit is 8 m/s, which almost coincides with that.
- A clear sky. A cloud passing in front of the sun changes the irradiance within seconds. The standard requires a maximum of 2/8 cloud cover.
In addition, the panels must be clean enough. Bird droppings or accumulated dirt produce a heat signal of their own that looks like a defect.
In Belgium that means: from late spring to late summer, around midday, on a clear day with little wind. A capture in November or under changing cloud cover may be technically possible to fly, but says little.
What the images do and do not show
A thermal drone capture is strong as a screening tool. You see the entire installation in a single flight, and every anomaly is given a location on the layout plan.
It does not show the cause. A warm panel can indicate a cell fracture, a diode fault, a loose connector, shade or dirt. The classification and the repair decision belong to your installer or PV specialist, who verifies the anomaly on site with a handheld camera or electrical measurements.
We therefore always deliver three things together:
- The thermal image per anomaly
- The visual image of the same spot, so that dirt and shade are immediately recognisable
- The radiometric files, so that your specialist can read out temperatures themselves
Together with the weather conditions and the irradiance at the time of the capture. Without that data, nobody can assess the measurement afterwards.
When it is worth it
- At handover of a new installation, as a baseline measurement for the warranty period
- In case of unexplained yield loss that the monitoring cannot locate
- After hail or storm, to document damage per panel for the insurer
- Periodically on large roofs, where a visual check from the ground shows nothing
For an installation of a few panels on a house, the ratio between preparation and information is less favourable. There, the inverter monitoring is often sufficient.
What we need from you beforehand
- The address and a layout plan or string diagram, if one exists
- Confirmation that the installation is in operation on the day of the flight
- A contact person on site for access to the roof or site
We plan the flight on a day that meets the measurement conditions. If the day does not qualify, we do not fly and we postpone the capture. A cancelled flight costs you a day; a capture under poor conditions costs you a wrong conclusion.
For this service: Roof & Facade, thermal assessments on request
Sources: IEC TS 62446-3:2017, Photovoltaic (PV) systems, Part 3: Outdoor infrared thermography of photovoltaic modules and plants.

